ADSS vs OPGW: Yuav Ua Li Cas Xaiv Txoj Cai Aerial Fiber Cable rau Koj Cov Hluav Taws Xob

Feem ntau ADSS vs OPGW kev sib piv qhib nrog ob lub ntsiab lus thiab kaw nrog lub rooj ntawm "qhov zoo." Lub rooj ntawd yuav tsis qhia koj qhov twg nyob ntawm koj kab.
ADSS vs OPGW
Cov Lus Qhia

Ob kab lus cais cov kab no hauv kev xyaum. Ib tug nqa nws tus kheej qhov hnyav thiab kov tsis muaj dab tsi hluav taws xob. Ib tug hloov koj cov av xaim thiab dhau los ua ib feem ntawm lub ntiaj teb.

Yog koj qhia, rov muag, los yog pom zoo siv dav hlau fiber ntau rau kev siv hluav taws xob hluav taws xob thiab kev lag luam hauv xov tooj, phau ntawv qhia no muab rau koj xaiv plaub-txheej txheem matrix tsis yog lwm daim ntawv teev npe. Nws kuj tau kho qhov kev xav uas tshwm sim hauv yuav luag txhua qhov kev sib tw sib tw - thiab hauv feem ntau RFQs peb tau txais.


Dab tsi tiag cais cov kab no

ADSS stands rau All-Dielectric Self-Supporting. All-dielectric txhais tau tias tsis muaj hlau nyob qhov twg hauv cable - lub zog los ntawm fiberglass-reinforced yas (FRP) Central tswv cuab thiab aramid yarn, tib tsev neeg fiber ntau siv hauv ballistic ntaub. Kev txhawb nqa tus kheej txhais tau hais tias nws nqa nws tus kheej qhov hnyav ntawm cov yees yam tsis muaj cov xaim sib cais.

OPGW stands rau Optical Ground Wire. Nws yog ib qho khoom siv hlau nplaum uas muaj cov khoom siv kho qhov muag kaw hauv lub raj stainless hlau. Nws ua txoj haujlwm koj cov nyiaj siv ua haujlwm hauv av twb tau ua - cuam tshuam xob laim thiab nqa qhov yuam kev tam sim no - thiab txav cov ntaub ntawv tib lub sijhawm.

Tam sim no qhov uas hloov koj qhov kev txiav txim siab:

  1. ADSS yog ib qho ntxiv rau koj cov kab. OPGW yog ib qho kev hloov ntawm cov kab txuas. Koj dai ADSS ntawm qhov chaw seem ntauwd. Koj nqa cov kab hauv av qub mus rau nruab OPGW.
  2. Tsuas yog OPGW nqa qhov yuam kev tam sim no. Nws muaj qhov ntsuas luv luv. ADSS tsis muaj qhov ntsuas zoo li no thiab yeej tsis yuav, vim nws ua tsis muaj dab tsi.
  3. ADSS feem ntau tuaj yeem ntsia tau yam tsis muaj hluav taws xob. OPGW yuav luag tsis tau. Hloov cov xaim hauv av txhais tau hais tias lub voj voog poob.

Kev Tshawb Fawb Txog Tus Neeg Yuav Khoom: Thaum tus neeg muag khoom hais ob qho kev xaiv, thawj lo lus nug tsis yog nqe. Nws yog qhov no: puas yog txoj kab no twb muaj ib txoj kab hauv av, thiab tus tswv puas xav kov nws? Yog teb yog “tau, muaj ib, thiab tsis muaj, peb tsis kov nws,” OPGW tawm ntawm lub rooj ua ntej tus nqi nkag rau hauv kev sib tham.

Qhov kev xav yuav luag txhua qhov kev qhia ua yuam kev

ADSS tsis yog ib yam khoom.

Ib lub tsho loj thiab ob lub tsho ADSS tau tsim txawv, mus txog qhov sib txawv, thiab muaj sia nyob txawv huab cua. Ntawm qee qhov kev txiav txim siab hloov pauv, qhov sib txawv ntawm lawv yog dav dua qhov sib txawv ntawm ADSS thiab OPGW.

Ib lub tsho ADSSOb lub tsho ADSS
Tswv yim span qab nthab300 mKilometer-chav kawm hla kev
ntug hiav txwv ntsev pos huab, daus hnyav, icingTsis haumTsim nyog
Ntxiv kev pab cuam lub neej nyob rau hauv cov huab cuaLub hauv paus+10 rau 15 xyoo
Standard fiber suav qab nthab144 (288 ntawm kev thov)288 (576 ntawm kev thov)
kwv tij tus nqi yuav khoomLub hauv paus+20% rau 25% ntawm qhov sib npaug ntawm fiber ntau

Nyeem thawj kab ntawd dua. Ib qho tshwj xeeb sau los ntawm ib kab lus dav dav - “ADSS ncua mus txog 1,000 m” - yog qhov tseeb rau ib qho kev tsim kho thiab tsis yog los ntawm ib qho ntawm peb rau lwm qhov. Peb pom qhov kev sib tsoo no hauv kev nug tiag: ib tug neeg xa ib 600 m span yuav tsum quoting ib leeg-lub tsho tsho tus nqi lawv pom lwm qhov.

Yog li los ntawm no mus, phau ntawv qhia no kho qhov kev xaiv raws li peb txoj kev, tsis yog ob txoj kev.


Hloov pauv 1 - Chav Kawm Voltage thiab Qhov Kev Xav Tau Li Cas

Voltage class shapes qhov kev txiav txim los ntawm ob qho kawg: nws txiav txim siab seb OPGW xav tau kev ntsuas hluav taws xob tshwj xeeb, thiab nws txiav txim siab nyuaj npaum li cas ib puag ncig ntawm lub tsho ADSS.

Dab tsi tsuas yog OPGW coj tuaj rau lub rooj

Vim OPGW hloov cov hlau hauv av, nws txais cov khoom siv hluav taws xob ua haujlwm ntawd. Ob tus lej tswj hwm qhov tshwj xeeb, thiab tsis muaj qhov sib npaug ADSS:

  • Short-circuit thermal muaj peev xwm (I² t) - Ntau npaum li cas txhaum lub zog lub cable absorbs ua ntej tus neeg xyuas pib overheats thiab fibers hauv ua noj.
  • DC tsis kam - uas yuav tsum tau zaum ze rau hauv av xaim ntawm lwm sab ntawm kab, los yog ob qhov sib koom tam sim no tsis sib xws thiab ib qho khiav kub.

Ntawm no yog tus neeg sawv cev 48-fiber configuration peb tsim, yog li koj tuaj yeem pom cov lej no zoo li cas hauv kev xyaum:

ParameterTus nqi
Txhawb nqa hla ntu64.51 mm² os
Rated Tensile zog (RTS)71.37 txhos caug
Short-circuit thermal muaj peev xwm (I² t)28.80 kA²·s
Lub sijhawm luv luv tam sim no (1 s, 20 ° C → 230 °C)5.37 kA
DC tsis kam1.161 Ω/km
Kev ntxhov siab txhua hnub (EDS)16-25% RTS
Ua haujlwm kub-40 ° C rau +80 °C
Cable taub / Tag nrho cov optical thiab mechanical Performance index ua tau raws li txoj hlua khi txheem11.10 mm / 429.64 kg/km

Qhov loj ntawm cov hlau ntoo hla ntu nce ob qho tib si qhov ntsuas qhov ua txhaum thiab lub zog tensile. Cov ntu me me raug nqi tsawg thiab thauj cov pej thuam tsawg dua. Koj daim phiaj tus neeg ua haujlwm qhov kev tshawb nrhiav txhaum cai teeb tsa hauv pem teb.

optical av xaim cable qauv

Distributor's Talking Points: Thaum tus neeg siv khoom siv npe hu ua chav kawm voltage thiab nres rau ntawd, koj tseem tsis tuaj yeem hais OPGW. Nug rautxhaum tam sim no thiab clearing lub sij hawm - ob tug tsim qhov yuav tsum tau I²t - thiab nug dab tsitam sim no hauv av xaim DC tsis kam yog. Nug cov no hloov koj los ntawm tus nqi-tus neeg siv khoom mus rau hauv kev sib koom ua ke, thiab nws yuav siv ib qho lus.

Dab tsi voltage ua rau ADSS

ADSS tsis ua dab tsi, yog li qhov hluav taws xob tsis cuam tshuam nws hluav taws xob nyob rau hauv txoj kev nws stresses tus neeg xyuas pib. Kev ntxhov siab yog nyob ntawm lub tsho nto.

Nyob ze energized conductors, ib daim teb hluav taws xob tsim nyob ib ncig ntawm lub cable. Qhov chaw paug thiab noo noo ua kom pom tseeb ntawm thaj chaw ntawd rau hauv thaj ua rau me me qhuav, thiab rov ua micro-tso tawm erode polyethylene dhau sijhawm. Kev ua tsis tiav yog qeeb. Nws feem ntau tshwm sim ib mus rau peb xyoos tom qab commissioning, uas txhais tau hais tias qhov kev txiav txim siab yuav thiab qhov tshwm sim tau sib cais los ntawm ntau lub sijhawm uas tsis muaj leej twg txuas rau lawv.

Qhov kev ntsuas yogAT (tiv thaiv kev taug qab) tsho sib xyaw tsis yog tus qauv PE. Peb muab ob qho tib si, sib pauv, hauv 1.6 mm, 1.8 hli thiab 2.0 mm phab ntsa thicknesses, nrog 1.8 mm ± 0.1 hli raws li peb tus qauv.

adss qauv

Cov lus qhia Pro rau cov neeg yuav khoom: Nug koj tus neeg muag khoom kom paub meej, sau ntawv, lub tsho sib xyaw thiab phab ntsa tuab ntawm cov lus hais - tsis yog “ADSS kab.” Ob nqe lus uas zoo li 15% Sib nrug feem ntau yog qhov sib txawv PE-tiv-AT, thiab cov khoom pheej yig dua tsuas yog pheej yig dua kom txog rau thaum thawj zaug yaig-tsav kev kho.

Ib daim ntawv ntawm cov rooj xaiv: voltage-chav kawm cov lus pom zoo nyob hauv kev lag luam qhia txog kev coj ua, tsis yog universal law. Daim phiaj kab sib txawv nyob hauv Latin America, Africa thiab Middle East, thiab qhov project tsim lub koom haum lossis chav haujlwm hluav taws xob engineering tuav qhov kawg hais. Kho txhua lub rooj hauv phau ntawv qhia no - suav nrog peb li - ua qhov pib rau kev sib tham ntawd.


Hloov pauv 2 -Span Length, thiab Vim Li Cas Ib Zaug Tsis Muaj Lus Teb

Span yog qhov twg cov khoom lag luam ua kev puas tsuaj ntau tshaj plaws, vim lawv hais ib qhov siab kawg nkaus.

Daim duab span tsuas txhais tau tias ib yam dab tsi nrog peb lwm yam mob: cua loading, dej khov loading, thiab tso cai sag. Tib lub cable uas yooj yim hla 300 m nyob rau hauv ib qho chaw ntsiag to yuav tsis tuav tib qhov kev ncua deb hla lub roob uas pom nrog cov dej khov radial.

Rau ADSS tshwj xeeb, span muaj peev xwm los ntawm aramid los yog polyester yarn strand suav thiab lub tsho qauv - tsis yog los ntawm fiber ntau suav thiab tsis yog los ntawm txoj kab uas hla. Tias yog vim li cas span yog ib tug engineered parameter koj xaj kom, es tsis yog cov khoom ruaj khov koj saib.

Span bandIb lub tsho ADSSOb lub tsho ADSSOPGW
Hauv qab 100 mYooj yimTshaj qhiaUa haujlwm, yog tias txoj kab xav tau av xaim lawm
100– 200 mStandard cheeb tsamYooj yimUa haujlwm
200– 300 mSiab txwvYooj yimUa haujlwm
300– 1000 mTsis muajTsim rau nwsUa haujlwm, RTS-nyob
Tshaj 1000 mTsis muajTshwj xeeb engineeringUa haujlwm, RTS-nyob

Peb tsim ib lub tsho ADSS rau 100 m, 150 m, 200 m thiab 300 m span ratings.300 m yog qab nthab, tsis yog hom phiaj - thiab nws poob thaum koj thawb suav fiber ntau. Ib lub tsho 288-fiber ib lub tsho tsim, piv txwv li, xav tau lub span tuav rau roughly 100 m, vim lub cev hnyav dua noj cov nyiaj txiag nro.

Distributor's Talking Points: Thaum tus neeg siv khoom hais “600 m span,” peb cov lus nug tom qab daws cov lus hais: Dab tsi yog qhov tsim cua ceev? Puas muaj dej khov? Dab tsi sag tso cai ntawm kev hla? Yog tsis muaj cov, ib qho kev cog lus ncua sij hawm yog kwv yees - thiab kev kwv yees yog dab tsi tau rov qab los.


Hloov pauv 3 - Tshiab Tsim lossis Retrofit, thiab seb koj puas tuaj yeem tua hluav taws

Qhov kev hloov pauv no txiav txim siab ntau txoj haujlwm tshaj li tus nqi ua, thiab nws faib kom huv si.

Tshiab kis kab

Ib txoj kab tshiab xav tau ib txoj kab hauv av tsis hais. Tus pej thuam raug tsim los lawm, qhov loading yog xam lawm, thiab cov neeg ua haujlwm stringing yog nyob rau ntawm qhov chaw lawm. Xaiv OPGW ntawm theem no txhais tau hais tiasnce ntxiv tus nqi tshaj ib txoj hlua hauv av yog me me - koj tab tom yuav fiber ntau, tsis yuav ib qho kev sib cais installation.

This is the strongest argument for OPGW, and it has nothing to do with the cable beingbetter.

opgw application

Retrofitting a line already in service

Now the arithmetic inverts. Replacing an in-service ground wire with OPGW requires taking the circuit out of service — and the outage is rarely the cheap part.

Real-World Scenario: On a live network, an outage is not a scheduling detail. It goes through a dispatch approval queue, competes with maintenance windows already booked, and may require replacement generation or rerouted load for the duration. Project teams routinely find the outage window harder to secure than the cable is to manufacture. Fifteen working days for cable delivery means very little when the switching request sits in a three-month queue.

ADSS exists largely because of this problem. Vim nws tuav tsis muaj hlau, nws tuaj yeem ntsia tau rau ntawm qhov chaw seem ntauwd yam tsis tau ua ib feem ntawm lub tshuab hluav taws xob.

Nyob rau hauv-line installation tshwj xeeb: tag nrho-dielectric kev tsim kho ua rau nws ua tau raws li txoj cai. Seb puas tau tso cai raukoj kab nyob ntawm chav kawm voltage, cov txheej txheem ua haujlwm ntawm kev siv hluav taws xob, kev tsim nyog ntawm cov neeg ua haujlwm thiab cov cuab yeej cuab tam tso cai. Kho “ADSS tuaj yeem ntsia tau nyob” raws li cov lus nug rau koj qhov chaw siv hluav taws xob kev nyab xeeb, tsis yog raws li specification koj xav tau. Peb zoo siab los muab cov ntaub ntawv cable rau koj qhov kev xav tau kev nyab xeeb; peb yuav tsis qhia koj tias txoj haujlwm muaj kev nyab xeeb ntawm kab peb tsis tau pom.


Hloov pauv 4 - Tag nrho cov nqi ntawm cov tswv cuab, Tsis Nqe Ib Meter

Nqe-ib-meter sib piv ntawm ADSS thiab OPGW yuam kev, vim ob leeg tsis yuav ib yam. OPGW tus nqi suav nrog cov xaim hauv av uas koj yuav txwv tsis pub yuav. ADSS tus nqi tsis suav nrog hauv av vim ADSS tsis yog ib qho.

Plaub tus nqi blocks muaj nyob rau hauv kev sib piv loj. Feem ntau luam tawm kev sib piv npog thawj zaug thiab hla tus so.

Tus nqi thaivADSS (ib leeg)ADSS (ob npaug)OPGW
Khoom sivTsawg tshaj plaws - kwv yees li 25-40% hauv qab ob lub tsho, qhov sib txawv nqaim li fiber ntau nce+20-25% tshaj ib leeg ntawm qhov sib npaug fiber ntau suavSiab tshaj ib 'meter', tab sis suav nrog hauv av xaim ua haujlwm
Installation ua haujlwmLightest kab, tsis muaj tus neeg xyuas pib ua haujlwmTib txoj kev, hnyav dua kabKev tshem tawm hauv av thiab stringing; kev tuav hnyav tshaj plaws
Tus nqi hluav taws xobFeem ntau zam tauFeem ntau zam tauFeem ntau tsis tuaj yeem zam ntawm kev rov ua dua tshiab - feem ntau yog cov kab loj tshaj plaws
Ntauwd loading91 kg/km os 48 fibers128 kg/km os 48 fibers429.64 kg/km os 48 fibers
Lub sijhawm saib xyuas ntevJacket yaig thiab UV aging yog cov khoom saib+10-15 xyoo ntxiv lub neej nyob rau hauv huab cua hnyavHlau corrosion thiab downlead kev ncaj ncees yog cov khoom saib

Ntauwd loading naj npawb tsis muaj leej twg quotes

Saib ntawm kab plaub ntawd. tib yam 48 fibers, peb OPGW hnyav429.64 kg/km tawm tsam91 kg/km rau ib lub tsho ADSS - kwv yees 4.7 lub sij hawm hnyav dua - thiab txog 3.4 lub sij hawm hnyav dua ob lub tsho ADSS ntawm 128 kg/km.

Kev lag luam cuam tshuam: Ntawm kab tshiab, tus pej thuam yog tsim los rau qhov load thiab tus lej tsis yog qhov teeb meem. Ntawm kab laus, nws yog cov lus nug txog cov qauv uas tuaj txog lig thiab raug nqi nyiaj - kev ntsuas kev thauj khoom, thiab qee zaum kev txhawb zog. Ntauwd reinforcement tsis tshwm sim ntawm ib qho kev hais lus cable, uas yog vim li cas nws derails retrofit pob nyiaj siv.

Qhov twg tus nqi them ob lub tsho loj them rov qab

Them 20-25% ntau dua rau lub tsho thib ob zoo li kev txiav yooj yim thaum lub sij hawm tus nqi engineering. Hauv ntug hiav txwv ntsev pos huab, hnyav daus los yog icing tej yam kev mob, nws yog qhov txiav tsis ncaj ncees lawm.

Ib lub tsho ADSS yogtsis haum rau tej qhov chaw ntawd. Ntsev pos accelerates tshuaj tua kab mob ntawm lub tsho; ib zaug lub tsho raug cuam tshuam, lub aramid hauv qab poob nws kev tiv thaiv. Peb txoj haujlwm yog ncaj qha: nyob rau hauv siab ntsev pos huab los yog icing cheeb tsam, peb pom zoo ob lub tsho tshaj sab es tsis yog muag ib lub tsho tuab dua li kev ua haujlwm. Kev tsim kho ob lub tsho loj ntxiv qhov kwv yees10 rau 15 xyoo ntawm kev pabcuam lub neej nyob rau hauv cov xwm txheej ntawd, nrog rau kev tiv thaiv hluav taws xob zoo dua qub thiab ob txheej dej thaiv.

Peb siv tau qhov no nrog 720-teev ntsev tsuag tshuaj ntsuam thiab UV laus kuaj rau GB / T 18899-2023. Nug txhua tus neeg muag khoom uas kuaj kev laus uas lawv tau ua tiav, thiab tshaj pes tsawg teev.


Muab Nws Ua Ke - Plaub-Variable Xaiv Matrix

Txhua kab hauv qab no muaj cov lus pom zoothiab tus mob uas overturns nws. Qhov kev hloov pauv yog qhov tseem ceeb, vim tias koj qhov project thaum kawg yuav ntaus ib qho.

ScenarioQhov hluav taws xobSpanTsim homLean rauDab tsi overturns nws
Tshiab kis kab mobHV / EHVIb qhoPlug-in / Module Hom PLC Splitter los ntawm Tuam Tshoj-FibconetOPGWNtauwd tsim twb tsau thiab tsis tuaj yeem nqus tau cov load
Retrofit, av hlau nyob rau hauv zoo mobHV / EHV≤ 300 mRetrofitIb lub tsho ADSSNtug hiav txwv, icing, los yog high-contamination site → ob lub tsho
Retrofit, ntev hlaIb qho> 300 mRetrofitOb lub tsho ADSSKev tawg yog ua tiav thiab kev hloov kho hauv av xaim yog vim li cas → OPGW
Suburban faibMV≤ 200 mLos yogIb lub tsho ADSSHnyav muaj kuab paug los yog cov ntug hiav txwv raug → AT tsho, los yog ob lub tsho
Ntev-ntev qaumHV / EHVMixedPlug-in / Module Hom PLC Splitter los ntawm Tuam Tshoj-FibconetOPGWTxoj kev hla qhov av uas tsis tuaj yeem teem sijhawm → ADSS
Txhua qhov project, huab cua hnyavIb qhoIb qhoLos yogOb lub tsho ADSS lossis OPGWNeither — do not put single-jacket into salt fog or icing

The variable this matrix cannot decide for you: fiber count

Almost no buying guide addresses fiber count, yet every purchase order requires the number.

Two principles apply. Ua ntej, build in headroom — utilities that specify only for today’s SCADA and protection traffic tend to return within a few years needing capacity for substation automation, video inspection or telecom backhaul, and a second cable pull costs far more than spare fibers ever did. Around 30% spare capacity is a common planning allowance.

Thib ob, respect the trade-off. More fibers means a heavier, thicker cable, which reduces achievable span. Our single-jacket ADSS runs 4 rau 144 fibers as standard, nrog 288 available on request when the span stays near 100 m. Double-jacket reaches 288 as standard and 576 ntawm kev thov. OPGW tops out at 96 fibers.

Cov lus qhia Pro rau cov neeg yuav khoom: Decide fiber countua ntej you finalise the span rating, not after. Fiber count changes the cable weight, cable weight changes the tension, and tension changes the span the cable can hold. Reversing that order is how projects end up re-ordering.


Field Traps That Appear After the Cable Is Already Hanging

Both cable types have well-documented failure patterns. Neither pattern is really about the cable.

On the ADSS side

  • Jacket erosion from the wrong compound. Standard PE in a high-field or high-contamination position degrades. AT compound exists for this reason. The symptom appears years later, far from the purchase decision.
  • Aeolian vibration. A light, all-dielectric cable in steady wind oscillates. Without dampers, the fatigue concentrates at the clamps.
  • Single-jacket in the wrong climate. Covered above — this is a specification error, tsis yog kev tsim khoom.
  • Fittings xav tias yuav interchangeable. Lawv tsis yog. Ib lub tsho loj thiab ob lub tsho ADSS muaj qhov sib txawv sab nraud, yog li kev ncua thiab tuag-kawg clamps loj rau ib qho yuav tsis raug tuav rau lwm tus. Cov peev nyiaj uas nqa tus nqi cable rau pem hauv ntej tab sis rov qab siv cov khoom qub fittings tuaj luv luv.

Ntawm OPGW sab - qhov twg qhov kev ua tsis tiav tiag tiag pawg

Qhov no yog ib feem yuav luag tsis muaj kev sib piv npog, thiab nws tsim nyog saib xyuas.

Kev tshawb nrhiav teb tom qab luam tawm cov qauv siv hluav taws xob teeb tsa taw qhia rau tib qhov kev txiav txim siab: OPGW tsis xws luag concentrate ntawm lubdownlead thiab splice termination, tsis nyob rau hauv lub span. Cov kab nruab nrab ntawm cov yees coj zoo. Qhov kev ua tsis tiav tshwm sim hauv ob peb meters kawg, qhov twg lub cable los ntawm tus qauv thiab nkag mus rau hauv splice enclosure.

Peb mechanisms tsav nws, thiab tag nrho peb yog physics es tsis yog kev cai hauv zos:

  • Poob ntawm insulating clearance. Qhov twg tus downlead txhais tau tias kom nyob twj ywm meej ntawm cov qauv, aging roj hmab clamps thiab corroding stainless bands cia lub cable drift mus rau hauv kev sib cuag. Tshem tawm erosion raws li, thiab strands tawg.
  • Dissimilar-hlau sib cuag. Stainless hlau banding tiv thaiv txhuas hlau teeb tsa galvanic corrosion. Band ua tsis tiav, ces qhov kev them nyiaj yug tsis.
  • Ferromagnetic khoom nyob ib ncig ntawm coiled slack cable. OPGW nqa tam sim no tsis tu ncua thiab ua txhaum tam sim no qee zaus. Coiling slack cable nyob rau hauv ib tug steel cia ncej, los yog khi nws nrog hlau hlau, coj zoo li ntxiv cov khoom tseem ceeb rau lub transformer - inter-tig induced voltage nce thiab kub hnyiab los ntawm strands. Rwb thaiv tsev, non-magnetic cia thav duab thiab aluminium daim kab xev khi zam nws.

Cov lus qhia Pro rau cov neeg yuav khoom: Thaum koj ntsuas qhov OPGW hais, saib dhau ntawm kab. Nug seb tus neeg muag khoom muab dab tsi raukev txiav txim pob - insulating downlead fasteners, non-magnetic cable cia thav ntawv, splice kaw, grounding hardware. Ib tug pheej yig cable nrog ib tug improvised downlead yog qhov twg lub sij hawm ntev txaus ntshai zaum. Peb muab cov cable thiab cov khoom siv ntxiv - preformed fittings, kev vibration dampers, muab qhab nia rings, splice kaw thiab cia racks - nyob rau hauv ib tug warranty, tshwj xeeb yog li kev sib tshuam ntawm lawv tsis muaj leej twg grey cheeb tsam.


Kab hauv qab - Peb Cov Lus Nug Nug Ua Ntej Txhua Tus Quotes Koj

Hla qhov kev sib piv feature. Peb cov lus nug no daws feem ntau ntawm kev txiav txim siab:

  1. Puas yog txoj kab no puas muaj cov kab hluav taws xob hauv av, thiab tus tswv yuav hloov nws? Tsis yog → ADSS. Yog → OPGW tiag tiag ntawm lub rooj.
  2. Qhov ntev tshaj plaws yog dab tsi, thiab cua thiab dej khov nyob ntawd yog dab tsi? Tshaj 300 m txiav txim tawm ib lub tsho ADSS tam sim ntawd. Cov ntug hiav txwv dej los yog dej khov ua rau nws tawm ntawm txhua qhov kev ncua.
  3. Dab tsi yog nyob rau hauv cov lus hais dhau ntawm kab? Jacket compound thiab phab ntsa thickness rau ADSS. I²t thiab DC tsis kam rau OPGW. Fittings, splice kaw thiab downlead hardware rau ob qho tib si. Ob lub ntsiab lus tsuas yog sib piv thaum lawv muaj tib qhov kev txwv.

Lub sij hawm tsim khoom siv lead ua tsis tshua muaj kev txiav txim siab, tab sis nws tsim nyog paub: peb Tshuag 12 rau 48-fiber ADSS nrog a 1 km yam tsawg kawg nkaus xaj, thiab txheem OPGW nkoj ntawm a 3 km yam tsawg kawg nkaus nrog ib tug raug 15 lub sijhawm ua haujlwm hnub. Kev pom zoo tsis pub dhau feem ntau yuav siv sij hawm ntev dua.

Tsis paub tseeb tias qhov twg haum rau koj txoj kab? Ib lub chaw tsim khoom uas tsim ob lub tsho ib leeg ADSS, ob lub tsho ADSS thiab OPGW tsis muaj laj thawj coj koj mus rau ib qho ntawm lawv. Xa peb chav kawm voltage, lub span profile thiab seb cov kab yog tshiab los yog nyob rau hauv kev pab cuam, thiab peb yuav qhia koj qhov twg ntawm peb qhov haum - suav nrog thaum cov lus teb yog qhov pheej yig tshaj. ADSS kab · Opgw cables


Technical cov duab hauv phau ntawv qhia no yog los ntawm peb tus kheej cov khoom specifications thiab lub Hoobkas kuaj. Voltage-chav kawm thiab ncua kev taw qhia qhia txog kev coj ua hauv kev lag luam thiab yuav tsum tau lees paub tiv thaiv kab lis kev cai thiab cov qauv tsim siv tau rau koj qhov project.

Tau txais Daim Ntawv Qhia Ceev

Peb yuav teb rau hauv 12 teev, thov xyuam xim rau email nrog cov lus tom qab “@fibconet.com”.

Kuj, koj tuaj yeem mus rau Hu rau nplooj ntawv, uas muab ib daim ntawv qhia ntxaws ntxiv.