Tarjimani tahrirlash
Qidirmoq

MPO dan MPO patch kabellari: Elyaf sonini tanlash, Magistral va Jumper havolalari uchun qutb va jins

Both ends take an MPO connector, so the hard part is not the connector. It is deciding which combination of fiber count, polarity and gender the link needs, and whether the two cords in that link fight each other.
mpo mpo patch cord ilovasi
Mundarija

Both ends take an MPO connector, so the hard part is not the connector. It is deciding which combination of fiber count, polarity and gender the link needs, and whether the two cords in that link fight each other.

This page covers configuration. If you are still working out what each field means on its own, theMPO patch cord selection guide covers the individual specifications first.

Patch Cord or Trunk — Two Different Jobs

An MPO to MPO assembly does one of two jobs, and the construction differs accordingly.

Yamoq kabeliTrunk
RolEquipment patching inside a cabinetPermanent backbone between cabinets or zones
Typical runShort, within a rack or between adjacent racksUzoq, spanning MDA, HDA and EDA zones
KurtkaSingle jacket, flexible for tight bendsHeavier construction, built for pulling and long-term strain
Elyaflar soni8 uchun 2412 uchun 144
Handled howHarakatlar va o'zgarishlar paytida ulangan va qayta ulanganBir marta o'rnatilgan, joyida qoldi
Ko'zni tortishQo'llanilmaydigan, qo'llab bo'lmaydiganA oxirida mavjud, B oxiri yoki ikkalasi

Mahsulot nomi sizga nima demaydi

Mahsulot nomidan ko'ra jismoniy talabga qarab buyurtma bering. Uni uchta maydon hal qiladi:

  • Ko'ylagi konstruktsiyasi — yamoq uchun moslashuvchan yagona ko'ylagi, doimiy yugurish uchun og'irroq qurilish
  • Uzunlik - marshrutlangan yo'l bo'ylab o'lchanadi, kabinetdan kabinetga emas
  • Ko'zni tortish — yig'ish quvur yoki laganda orqali tortilsa, talab qilinadi

O'rnatish vaqtida tortuvchi ko'z ulagichni himoya qiladi. Fibconet uni A oxirida ta'minlaydi, B uchi yoki ikkala uchi, va keyinroq qo'shilgandan ko'ra buyurtma vaqtida ko'rsatiladi. Kanal orqali tortilgan uzun magistralda, Himoyalanmagan MPO konnektorlarini sudrab olib borish - bu havola tekshirilgunga qadar oxirgi yuzlarning yo'q qilinishidir.

mpo patch kabeli R&D

Uzunlik bardoshliligi, va nima uchun bu magistrallarda ko'proq ahamiyatga ega

Fibconet gradusli tolerantlikka asoslanadi, har doim ijobiy:

Buyurtma qilingan uzunlikTolerantlik
ostida 1 m+5 / −0 sm
1 uchun 10 m+10 / −0 sm
10 uchun 40 m+15 / −0 sm
Ustida 40 m+0.5% uzunligi / −0

Har bir guruh faqat ijobiy ishlaydi, shuning uchun yig'ilish hech qachon qisqa kelmaydi. a kuni 100 gacha degan ma’noni anglatuvchi m trunk 50 sm qo'shimcha kabel, qaysi boshqaruvchiga o'raladi. Nosimmetrik bardoshlik uchun qurilgan shnur kelishi mumkin 50 sm qisqa, va yamoq paneliga etib bormaydigan magistral hurdadir.

Fibconet ularni shunday quradiLSZH MPO magistral agregatlari va bir xildan qisqaroq jumperlar sifatidaMPO/MTP yamoq kabeli diapazoni.

Ikki tomonlama MPO havolasi uchun tolalar soni va optik daraja

Kanal bo'ylab mos keladigan raqam

Tolalar soni qabul qiluvchidan keyin keladi: 840G va 100G SR4 yoki 400G SR8 uzilishlari uchun F, 12F umumiy parallel optika va tuzilgan magistrallar uchun, 16400G QSFP-DD va OSFP uchun F, 24F qaerda zichlik eng muhim.

Ikki uchli MPO havolasida hisoblash har bir segmentda bo'lishi kerak. 12F jumperni oziqlantiruvchi 12F magistral ishlaydi.

Kabel diametri hisobni kuzatib boradi. da ishlaydi 8, 12, 16 va 24 tolalar a foydalanadi 3.0 mm ko'ylagi; 3.8 mm va 4.5 mm konstruktsiyalar mavjud, mikro-tarqatish bilan birga, oval lenta va zirhli konstruktsiyalar yuqori sonlar yoki qattiqroq yo'llar uchun.

Qo'shishni yo'qotish va havolangizga nisbatan qaytarish yo'qolishini o'qish

Fibconet MPO agregatlarida ikkita yo'qotish darajasi mavjud:

Standart yo'qotishKam yo'qotish
Yagona rejim (APC)≤ 0.75 dB maks, 0.4-0,5 dB tipik≤ 0.35 dB maks, 0.2-0,25 dB tipik
Ko'p rejimli (Kompyuter)≤ 0.6 dB maks, 0.35-0,5 dB tipik≤ 0.35 dB maks, 0.2 dB tipik

Qaytish yo'qotilishi bitta raqam sifatida emas, balki oxirgi yuz bilan belgilanadi, chunki jilo geometriyasi aks ettirishni belgilaydi:

Yakuniy yuzYagona rejimKo'p rejimli
Kompyuter≥ 50 dB≥ 20 dB
APC≥ 60 dB≥ 40 dB

Qo'shish yo'qolishi va qaytarish yo'qolishi IEC bo'yicha o'lchanadi 61300-3-4 (kiritish usuli B), da 1310/1550 nm yagona rejim uchun va 850/1300 multimod uchun nm.

Kotirovkalarni solishtirganda raqam bilan birga test usulini so'rang, chunki bir xil yig'ilish turli usullarda turlicha o'lchaydi.

Chop etilgan maksimal qiymat faqat birlashma nuqtalarini sanab, ularni qo'shgandan keyin foydali bo'ladi:

Ishlagan misol. Jumper → magistral → kasseta → jumper bilan ishlaydigan tizimli kanal to'rtta MPO ulanish nuqtasini taqdim etadi. Multimode standart darajasida eng yomon holatlar to'planadi 4 × 0.6 dB, yoki 2.4 tolaning zaiflashuvidan oldin ulagichning yo'qolishi dB. Kam yo'qotish darajasida bir xil to'rt ball to'planadi 1.4 dB. Har bir raqamni qabul qiluvchi ma'lumotlar varaqidagi havola byudjeti bilan solishtiring.

Eski 40G yoki 100G havolasidagi bitta ulanish nuqtasi odatda standart sinfda ishlaydi. Ikki yoki undan ortiq ulanish nuqtalari, yoki har qanday 400G va 800G parallel ulanish, kam yo'qotishlarni talab qiladi.

Import qilingan ferrullar bilan qurilgan yig'ilishlar atrofni o'lchaydi 0.15 Oddiy ishlab chiqarish sinovlarida bitta rejimda yadro boshiga dB.

Bu o'lchovdagi odatiy qiymat, spetsifikatsiya chegarasi emas - belgilangan chegara saqlanib qoladi 0.35 past yo'qotish darajasi uchun dB.

Yetkazib beruvchi bitta ta'sirchan raqamni keltirganda, maksimal yoki odatiy ekanligini so'rang, chunki faqat maksimal shartnoma hisoblanadi.

mpo yamoq simi QC

Butun havola bo'ylab qutblanish, Bitta sim emas

Qutblilik tolalar joylashuvi xaritasini oxirigacha qanday tasvirlaydi. Bitta shnurda qoida oddiy. Ketma-ket ikkita yoki uchta shnurli kanalda, xaritalar birlashadi, va bu erda havolalar muvaffaqiyatsiz bo'ladi.

Tezkor xulosa: Xaritalar o'rnini A yozing 1 uchun 1 to'g'ridan-to'g'ri, B turi butunlay teskari 1 uchun xaritalar 12, C turi qo'shni juftlarni almashtiradi. To'liq maydon darajasidagi ta'riflarMPO patch simini tanlash bo'yicha qo'llanma.

To'g'ridan-to'g'ri havola: transceiverdan qabul qiluvchiga

Ikki parallel uzatuvchi o'rtasidagi bitta sim kanalning biron bir joyida bitta krossoverga muhtoj, va B turi uni shnurning o'zida etkazib beradi. Bu yangi tuzilmalar uchun standart hisoblanadi.

Strukturaviy havola: magistral, kasseta, jumper

Kanalda kassetalar bilan, krossover harakatlanadi. A tipidagi magistrallarga buyurtma bering va kassetaning polarit kompensatsiyasini bajarishiga ruxsat bering, eng tuzilgan tizimlar atrofida ishlab chiqilgan tartibga solish hisoblanadi.

A turi dupleks uchlarida e'tibor talab qiladi. Chunki A tipidagi magistral joylashuvni xaritalaydi 1 joylashtirish 1 burilishsiz, kanalning bir uchida A-B dupleks patch kabeli, ikkinchi tomonida A-A dupleks patch kabeli kerak.. Ikkala uchida va tolada A-B dan foydalaning 1 tolaga uzatadi 1, Rx-ni Rx-ga qarshi qo'yish, va havola muvaffaqiyatsiz tugadi.

Fibconet qo'llab-quvvatlaydiMPO kasetlari bu kompensatsiya uchun qurilgan.

Nima uchun ketma-ket ikkita B tipidagi simlar bekor qilinadi?

Har bir turdagi B shnuri xaritani bir marta aylantiradi. Ulardan ikkitasi ketma-ket ikki marta aylantiradi, bu kanalni to'g'ridan-to'g'ri yo'lga qaytaradi.

Kanal qachon o'sishi muhim. Ikki qabul qiluvchi o'rtasida to'g'ridan-to'g'ri B tipidagi aloqa ishlaydi. Panel orqali ulanishni kengaytirish uchun keyinroq ikkinchi turdagi B o'tkazgichni qo'shing, va kanalda endi ikkita burilish mavjud: pozitsiya 1 pozitsiyasiga keladi 1, uzatish uchrashadi, va kecha ishlagan havola ishlashni to'xtatadi.

Butun kanal bo'ylab burilishlarni hisoblang, shnur uchun emas. Kanalga ikkita qabul qiluvchi o'rtasida toq sonli krossoverlar kerak - bitta, yoki uchta, lekin ikkita emas.

Yangi qurilish uchun, B tipidagi har bir simni va har bir g'alati hisobni saqlash - bu kelajakdagi o'zgarishlarga eng kam o'ylash bilan omon qoladigan tartibga solishdir. C turi eski dupleks tizimlar uchun mavjud, va biz uni yangi parallel havolada ishlatmaymiz.

PIN konfiguratsiyasi - Buni noto'g'ri qabul qiling va u ulanmaydi

Erkak MPO konnektorlari ikkita hidoyat pinini olib yuradi; ayol konnektorlari mos keladigan teshiklarga ega. Har bir juftlashgan juftlik har biridan biriga muhtoj. Ikkita erkak konnektorda pinlar o'tiradigan joyi yo'q va umuman birlashmaydi.

Fibconet barcha uchta kombinatsiyani yaratadi, yig'ish uchun buyurtma qilingan:

KonfiguratsiyaQaerga mos keladi
Ayoldan ayolgaIkkala uchi ham uskuna portlari yoki kasseta portlariga tushadi, ular odatda erkaklardir
Ayoldan erkakkaUskunaning bir uchi, bir uchi ayol adapter yoki panelga
Erkakdan erkakkaIkkala uchi ham ayol adapterlari yoki kassetali portlarga tushadi

To'rtta ulanish nuqtasi bo'ylab jinsni xaritalash

Jins juftlashgan juftlikning xususiyatidir, shnurdan emas. Magistral va ikkita jumperli kanalda to'rtta ulanish nuqtasi mavjud, va har biriga bitta pin va bitta teshik kerak.

Ruxsat etilgan uchlardan orqaga qarab ishlang. Transceiver portlari va kasseta portlari jinsini siz o'zgartira olmaysiz, shuning uchun u erdan boshlang va kanal bo'ylab almashing. Umumiy tartibga solish, ayol konnektorlarni uskuna tomoniga va erkakni mahkamlangan magistral tomoniga qo'yadi, Garchi oldingizda turgan kasseta haqiqiy javobni hal qilsa.

Ayoldan ayolga ulanish kerak bo'lganda mpo erkakdan ayolga patch kabeliga buyurtma berish saytda tiklanmaydi.. Pimlar yig'ish paytida o'rnatiladi, shuning uchun noto'g'ri tartiblangan jins shnurni qayta buyurtma qilishni anglatadi. Buyurtmani chiqarishdan oldin simlar kelgandan keyin emas, balki har bir uchida portni tekshiring.

Agar siz noto'g'ri tushunsangiz nima bo'ladi

Ikki xil nosozliklar chaqiriladi “polarit muammosi”, va ularning turli egalari bor.

Ishlab chiqarishdagi xatolar Ipni ulash paytida tolalar ketma-ketligi yoki qutblilik noto'g'ri tuzilganda sodir bo'ladi.

Fibconet har bir yig'ilishda har bir yadroni kiritish yo'qolishi uchun sinovdan o'tkazadi, qaytish yo'qotilishi, oxirgi yuz, qutblanish, tolalar ketma-ketligi, uzunligi va tashqi ko'rinishi, shuning uchun bu sinf saytingizda emas, balki jo'natishdan oldin ushlangan.

Spetsifikatsiyadagi xatolar buyurtma qilingan konfiguratsiya kanalga mos kelmasa sodir bo'ladi. Zavod buyurtmada ko'rsatilgandek quradi, Har bir yadro sinovdan o'tadi, va shnur hali ham ushbu havolada ishlamaydi. Hech qanday zavod sinovlari buni ushlay olmaydi, chunki shnurda hech qanday muammo yo'q.

Quyidagi jadval ikkinchi sinfni qamrab oladi:

Noto'g'ri belgilanganU paydo bo'lgandaTashxis qo'yish qanchalik qiyinSaytda tuzatish mumkin
JinsUni rozetkaga ulashga harakat qilgan paytingizDarhol va aniqYo'q. Pinlar yig'ilishda o'rnatiladi; qayta buyurtma berish
Elyaflar soniPortda, yoki quvvat yoqilgandaPast. Ulagichda ko'rinadiYo'q. Qayta buyurtma berish
PolarlikQuvvat yoqilganda. Jismoniy jihatdan birlashtirilgan, pastga bog'langEng yuqori. Everything looks connectedYo'q. Re-order the correct type
Loss gradeLink comes up, then runs short on marginYuqori. Presents as a transceiver or fiber problemYo'q, but a link budget recount confirms it

None of these four is fixable in the field, which puts the whole cost of getting it wrong into the RFQ. Confirming four fields before the order costs one email.

Configuration Matrix by Use Case

Find the row that matches your channel:

Use caseFormElyaflar soniPolarlikJinsBaho
Transceiver to transceiver, same rack, 40G/100G SR4Jumper12F (or 8F)B turiAyoldan ayolgaStandart, single mating point
Transceiver to transceiver, 400G/800G parallelJumper8F or 16FB turiAyoldan ayolgaKam yo'qotish
Backbone between cabinets, feeding cassettesMagistral12F or 24FA turiErkakdan erkakka (into cassette)Low loss if ≥2 mating points
Cassette to switch, structured channelJumper12FB turiAyoldan ayolgaKam yo'qotish
High-density backbone, hyperscale rowMagistral24F to 144FA turiPer cassetteKam yo'qotish
Extending an existing Type B direct linkJumperMatch existingCount total flips, keep oddPer portsMatch existing
Legacy duplex-based systemYoki12FC turiPer portsStandart

Stocking guidance for distributors: new-build data centre demand concentrates on Type B female-to-female jumpers in 12F multimode, since that is what direct transceiver connections take.

Structured-cabling projects pull Type A trunks with the crossover handled in the cassette. Holding both patterns covers most incoming enquiries without stocking every permutation.

Send the matrix row plus length and quantity with your enquiry and we can quote against a fixed configuration.

How These Assemblies Are Built and Tested

Every assembly is tested core by core before shipment: kiritish yo'qolishi, qaytish yo'qotilishi, oxirgi yuz, qutblanish, tolalar ketma-ketligi, uzunligi va tashqi ko'rinishi. Electronic test reports are available after order placement.

Core-by-core testing exists because of where MPO defects originate. Polarity reversal and sequence errors happen during ribbon splicing, and they produce an assembly that looks correct and measures correct on any single core. Sampling one core in ten does not find them. Fibconet splices with high-precision ribbon fusion equipment and verifies the full mapping on the finished assembly.

End-face geometry is measured by 3D interferometry against these limits:

ParametrLimit
Radius of curvature, X≥ 2000 mm
Radius of curvature, Y≥ 50 mm
Angle, APC7.85° to 8.15°
Fiber height1000 uchun 3500 nm
Adjacent fiber height difference±300 nm

Those numbers decide whether twelve fibers make physical contact simultaneously.

Tezkor taklif oling

Biz ichida javob beramiz 12 soat, qo'shimchasi bilan elektron pochtaga e'tibor bering “@fibconet.com”.

Shuningdek, ga borishingiz mumkin Aloqa sahifasi, batafsilroq shaklni taqdim etadi.