فیبر نوری Pigtail معنی: انواع, Selection and Splice-Tray Installation

A fiber optic pigtail is a short length of fiber with a factory-terminated connector on one end and bare fiber on the other. The bare end is fusion spliced to an incoming cable inside a splice tray, ODF or termination box, and the connector plugs into an adapter on the front panel. A typical order line looks like this: SC/APC pigtail, G.657.A1, 0.9 mm tight buffer, 1.5 متر, رنگ زرد. Every field in that line is a decision. This guide covers the five that matter: buffer construction, اتصال دهنده و پولیش, نوع فیبر, fiber count and length, and then how to install and check the pigtail once it is spliced.
پیگتیل فیبر نوری
فهرست مطالب

فیبر نوری Pigtail چیست؟

In a link, the pigtail sits between the cable and the patch panel: incoming cable → fusion splice → pigtail → adapter → patch cord → equipment. Its job is to give a field-spliced cable a factory-polished connector, so the end face that carries the optical connection is made and tested on a production line, not in a manhole or a cabinet.

A patch cord has connectors on both ends and runs between two adapters or between an adapter and equipment. If you need a full side-by-side comparison of loss specs, polish types and when to use each, راهنمای ما را ببینید difference between fiber pigtails and patch cords.

How a Pigtail Is Built: 250 میکرومتر, 0.9 mm Buffer and Jacketed Versions

Every single-mode or multimode pigtail starts with the same glass: آ 125 µm cladding with a 250 µm acrylate coating. What changes is what is put over that coating.

ساخت و سازقطر خارجیاستفاده معمولیHandling note
Coated fiber250 میکرومترHigh-density splice trays, ribbon-style closuresFragile; route only inside protected trays
Tight buffer0.9 میلی مترStandard indoor pigtail for ODFs and termination boxesBuffer strips back to 250 µm before splicing
Semi-tight buffer0.9 میلی مترSame applications; buffer strips off in longer lengths with less forceChoose by stripping preference, not by optical performance
Jacketed (سیمپلکس)2.0 میلی متر یا 3.0 میلی مترPigtails routed outside a tray, or exposed to handlingAramid yarn and jacket must be cut back and anchored at the tray entry

Tight and semi-tight 0.9 mm buffers are both standard specifications. در 0.9 mm figure is the buffer’s outer diameter; the glass inside is still 125 میکرومتر.

Coated fiber 250 µm coating Buffered fiber 0.9 mm tight or semi-tight Jacketed pigtail 2.0 / 3.0 میلی متر, aramid yarn inside Not to scale. Glass cladding is 125 µm in all three.
Three pigtail constructions. The glass is identical; the buffer and jacket decide where the pigtail can be routed.

Pigtail Types by Fiber Count

Most orders are single-fiber (سیمپلکس) خوکچه ها. When a tray terminates many fibers at once, a bundle pigtail is faster to install: 4, 6, 8, 12, 24 or more fibers share one jacket and fan out into individual buffered fibers, each with its own connector. Fibconet multicore bundle pigtails follow the TIA-598 fiber colour code, so fiber 1 is blue, فیبر 2 is orange and so on through 12. Overall length and fan-out length are built to order.

1 آبی 2 نارنجی 3 سبز 4 رنگ قهوه ای 5 سنگ لوح 6 سفید 7 قرمز 8 مشکی 9 رنگ زرد 10 بنفش 11 گل سرخ 12 آبی Fiber identification sequence per TIA-598. Map fiber 1 to adapter port 1 unless the project drawing says otherwise.
TIA-598 sequence for fibers 1 به 12, used on Fibconet bundle pigtails.

Choosing the Connector and Polish

The connector must match the adapter already fitted in the ODF or box; the pigtail is the part you change, not the panel.

رابطWhere you usually meet itPigtail note
SCFTTH termination boxes, ODF, پریزهای دیواریMost common simplex pigtail
LCHigh-density ODFs, data center panelsHalf the footprint of SC; check duplex clip needs
اف سیOlder telecom ODFs, ابزار آزمایشThreaded coupling
STLegacy multimode and industrial panelsBayonet coupling

For a direct comparison of the two most common choices, ببینید SC vs LC patch cords.

Polish is the second half of the decision. UPC end faces are domed; APC end faces are angled at 8°. They cannot be mated with each other. در TIA-568 connector colour code makes the check visual: single-mode UPC connectors are blue, single-mode APC connectors are green, multimode is beige. If the adapter is green, order APC pigtails. What happens to loss and the end face when the two are mixed is covered in our pigtail vs patch cord guide.

Fibconet indoor pigtails are specified at insertion loss ≤0.3 dB per mated connector pair, with return loss ≥50 dB for UPC and ≥55 dB for APC (supplier-stated specification). Each pigtail is tested for insertion loss, return loss and end-face condition before shipment; test reports are provided on request and confirmed at quotation.

Matching the Pigtail Fiber to the Incoming Cable

Single-mode and multimode fibers cannot be spliced together, and multimode grades (OM1 به OM5) should match the cable they join. For single-mode, the practical question is G.652.D versus G.657.

G.657 fibers are bend-insensitive. ITU-T G.657 (11/2016), جدول 1 sets these maximum macrobending losses for uncabled fiber at 1550 نانومتر:

دستهBend radius × turnsMax loss at 1550 نانومترMax loss at 1625 نانومتر
G.657.A110 میلی متر × 1 چرخش0.75 دسی بل1.5 دسی بل
G.657.A210 میلی متر × 1 چرخش0.1 دسی بل0.2 دسی بل
G.657.A27.5 میلی متر × 1 چرخش0.5 دسی بل1.0 دسی بل

These are standard limits for bare, uncabled fiber, not installed performance. The same Recommendation notes that G.652 fibers bent to 15 mm can lose several dB per 10 می چرخد ​​در 1625 نانومتر, which is why a G.652.D pigtail should never be looped as tightly as a G.657.A2 one.

G.657.A fibers are designed to be compatible with G.652.D, so a G.657.A1 or A2 pigtail can be fusion spliced to a G.652.D cable. If the network will carry 1625 nm monitoring or XGS-PON wavelengths and the tray is compact, G.657.A2 pigtails give the most bend margin.

How Long Should a Pigtail Be?

The indoor pigtail standard length is 1.5 متر, and lengths are made to order. Whether 1.5 m is enough depends on the tray, not on a rule of thumb. Calculate it:

Pigtail length = routing length (adapter to tray entry) + loops × π × loop diameter + re-splice allowance

  • Routing length: measure the path from the back of the adapter to the splice tray entry along the actual cable guides.
  • Loop diameter: set by the tray’s storage area. It must be at least twice the minimum bend radius of the fiber you use.
  • Re-splice allowance: each failed or repaired splice consumes fiber for stripping and cleaving. Leave enough for at least one re-splice.

Worked example with illustrative inputs (replace them with your tray’s values): routing length 0.30 متر, two storage loops at 60 قطر میلی متر (2 × π × 0.06 = 0.38 متر), re-splice allowance 0.30 متر. مجموع: در باره 0.98 متر. آ 1.5 m pigtail leaves roughly 0.5 m extra, which goes into one more storage loop. آ 1.0 m pigtail would leave almost nothing for a second repair.

If the ODF also needs a capacity plan, ما ODF guide covers tray counts and port sizing.

Installing a Pigtail in a Splice Tray

آداپتور اسپلایس + sleeve Incoming cable Storage loops (diameter ≥ 2 × min. شعاع خم شدن) Not to scale. Layout varies by tray; keep every bend within the fiber’s minimum bend radius.
Pigtail path inside a splice tray: آداپتور, storage loops, protected splice, incoming cable.
  1. Route the pigtail from the adapter to the tray entry. Keep jacketed sections anchored at the entry and do not let the buffer rub on sharp edges.
  2. نوار, clean and cleave. Strip the 0.9 mm buffer back to the 250 µm coating, then remove the coating, clean the glass and cleave. Fit the splice protection sleeve onto one fiber before splicing.
  3. اتصال فیوژن. Align and fuse the pigtail fiber to the cable fiber. The splicing process itself is covered in how a fusion splicer works.
  4. Protect the splice. Slide the heat-shrink sleeve over the joint and shrink it. Sleeves are commonly 40 میلی متر یا 60 mm long and sized for 250 µm to 0.9 فیبر میلی متری; use the length your tray holder is designed for.
  5. Store the slack. Lay the remaining fiber in loops inside the storage area. No bend should be tighter than the fiber’s minimum bend radius.
  6. Label. Mark the tray and adapter port with the fiber number and colour so the next technician can trace it.

For jacketed cable outside the tray, را FOA bend radius guideline است 20 times the cable diameter under pulling tension and 10 times after installation, unless the cable manufacturer specifies otherwise.

What to Check After Splicing

Three checks answer three different questions. Do them in this order.

بررسی کنیدآنچه به شما می گویدPass rule
Fusion splicer loss estimateWhether the splice is obviously bad before you sleeve itRe-splice if the estimate is higher than your project limit. در FOA loss budget guidance استفاده می کند 0.15 dB per single-mode fusion splice for planning; modern splicers commonly report well below that
ردیابی OTDRWhere each splice and connector is and how much each losesTest from both ends and average the splice loss; a single direction can show a false gain or exaggerated loss when the two fibers differ
End-to-end insertion lossWhether the whole link meets its budgetMeasured loss ≤ calculated budget (فیبر + اتصال دهنده ها + شکاف). The FOA guidance uses 0.3 dB per connector

The splicer estimate is not an acceptance test, and an OTDR does not replace end-to-end insertion loss testing when the project specification calls for it. If you are choosing an instrument for the second step, ببینید how to choose an OTDR.

When a link fails, the factory test record of the pigtail separates connector loss from splice loss: the connector was measured before shipment, so a high reading at the splice event points to the field joint.

Pigtail Splicing or Field-Installable Connector: Cost per Termination

Both methods put a connector on a field cable. The cheaper one depends on the job, so compare them per completed termination:

Cost per good termination = component price ÷ first-pass yield + (labour time × labour rate) + rework consumables + equipment cost ÷ terminations per year

Factorدم خوک + شکاف همجوشیField-installable connector
Component pricePigtail plus splice sleeveیک کانکتور
Connector end faceFactory-polished and testedFactory-prepared ferrule, assembled in the field
Labour timeDepends on site: access, tray density, crew experienceDepends on site; usually shorter per point, no splicer needed for mechanical types
First-pass yieldDepends on splicer condition, cleaver and crewDepends on cleave quality and cleanliness; a failed connector is discarded
Planning loss0.15 dB per splice plus 0.3 dB per connector (FOA)0.3 dB for fusion splice-on types; تا 0.75 dB for mechanical/prepolished types (FOA)
تجهیزاتاسپلایسر فیوژن, cleaverCleaver; fusion splicer only for splice-on types

Labour time, labour rate and first-pass yield vary too much between sites to give a single figure. Use your own crew’s numbers. Yield matters more than it looks: در 95% first-pass yield every component costs 1/0.95 = 1.05 times its price, در 90% it costs 1.11 بار, and at 85% it costs 1.18 بار, before counting the labour spent on the failed attempts.

As a rule: pigtails suit ODFs and trays that terminate many fibers in one place with a splicer already on site; field-installable connectors suit scattered single drops where carrying a splicer to each point costs more than the connectors.

How to Write a Pigtail Order Line

میدانمثالDecided by
رابطSCThe adapter in the panel
لهستانیAPCAdapter colour and system design
نوع فیبرG.657.A1The incoming cable and tray bend radius
Buffer0.9 mm tight bufferTray type
تعداد فیبرسیمپلکس, or 12-fiber bundleNumber of ports per tray
طول1.5 مترLength calculation above
Colourرنگ زرد (حالت تک), or TIA-598 for bundlesFiber type and project standard
Test documentationIL/RL report on requestProject acceptance requirements

Send these eight fields with the quantity and you have a complete specification. Fibconet محدوده پچ کورد و پیگتیل covers each combination above; request the IL/RL report at quotation if your acceptance procedure needs it.

سوالات متداول

What is the difference between a pigtail and a patch cord?

A pigtail has a connector on one end and bare fiber on the other, and it is fusion spliced to a cable. A patch cord has connectors on both ends and plugs into adapters or equipment. در pigtail vs patch cord guide compares them in detail.

Can I cut a patch cord in half to make two pigtails?

آره, optically it works: each half becomes a pigtail with a factory connector. Check two things first. Most patch cords use 2.0 میلی متر یا 3.0 mm jacketed cable, which needs more room at the tray entry than a 0.9 mm pigtail, and the jacket and aramid yarn must be anchored. Also make sure the cord’s fiber type matches the incoming cable.

How much pigtail length should be left in an ODF?

Calculate it from the routing length, the number and diameter of storage loops, and a re-splice allowance. With illustrative inputs of 0.30 m routing, two 60 mm loops and 0.30 m re-splice allowance, the total is about 1 متر, which is why 1.5 m is the common indoor pigtail length. Replace the inputs with your tray’s dimensions.

What is the colour order of a 12-fiber pigtail?

Under TIA-598 the order is blue, نارنجی, سبز, رنگ قهوه ای, slate, سفید, قرمز, سیاه, رنگ زرد, بنفش, rose, آبی. Fibconet bundle pigtails follow this sequence.

Is a fiber pigtail 0.9 میلی متر یا 250 میکرومتر?

Most indoor pigtails use 0.9 mm buffered fiber, either tight or semi-tight buffer. در 0.9 mm is the buffer’s outer diameter; it is stripped back to the 250 µm coating, and then to the 125 µm glass, قبل از اتصال. 250 µm pigtails are used in high-density trays.

Can a G.657.A2 pigtail be spliced to G.652.D cable?

آره. G.657.A fibers are designed to be compatible with G.652.D fibers, so they fusion splice normally. Test the splice from both directions with an OTDR, because the two fibers can show an apparent gain in one direction and an exaggerated loss in the other.